Liebert XDU
Cooling Distribution Unit
Optimized for artificial intelligence (AI) and GPU-intensive workloads, Liebert XDU provides continuous liquid distribution for direct-to-chip cooling and rear-door heat exchangers.
Future-Ready Hybrid Cooling
Liebert XDU Cooling Distribution Unit
Future-ready liquid cooling infrastructure for Artificial Intelligence (AI) and High-Performance Computing (HPC) workloads.
Designed to provide high-density cooling in data centers, Liebert XDU offers cost-effective, easy-to-deploy solutions for direct-to-chip and rear-door heat exchanger (RDHx) applications.

Flexible Integration
Supports rapid integration into different data center environments, with or without access to facility cooling water.
AI and HPC Ready
Its 1368 kW nominal capacity supports demanding GPU workloads and direct-to-chip cooling requirements in high-density racks.
Fully Redundant Protection
An N+1 redundant pump system, integrated 50-micron filtration and leak detection support continuous operation for critical workloads.
Ideal Applications
Designed for AI and High-Density Facilities
Liebert XDU is a critical component in the transition from traditional air cooling to high-performance liquid cooling. It provides secure and precise heat transfer of up to 1368 kW between the facility loop and the server cooling loop, supporting the direct-to-chip cooling requirements of AI and HPC servers.
Recommended Applications
Why Choose Liebert XDU?
Critical System Protection and Loop Integrity
Liebert XDU completely separates the data center facility loop from the sensitive secondary loop, eliminating leakage and contamination risks.


High-Performance Thermal Management and Intelligent Control
Developed for demanding AI and HPC workloads, Liebert XDU responds immediately to dynamic heat loads and maintains server-level thermal stability.
|
Feature
|
Technical Detail / Value
|
|---|---|
|
Nominal Cooling Capacity |
1368 kW at 7.2°F / 4°C ATD |
|
Maximum Cooling Capacity |
2912 kW at 14.4°F / 8°C ATD |
|
Nominal Flow Rate – 2 Pumps |
1,200 L/min (317 gpm) |
|
Maximum Flow Rate – 3 Pumps |
1,800 L/min (475.5 gpm) |
|
Secondary-Loop Coolant |
Water, water/glycol or compatible single-phase fluids |
|
Pump Redundancy |
N+1 dual-pump or N three-pump operating modes |
|
Temperature Control Range |
10°C to 52°C (50°F–126°F), with standard dew-point control |
|
Dimensions – H × W × D |
2069 × 900 × 1243 mm |
|
Weight |
Approximately 650 kg (1,433 lb) |
|
Communications and Monitoring |
RS-485 RTU Modbus, TCP/IP, SNMP, CLI and web interface |
Technical Article: XDU070 Hybrid Liquid Cooling Solution
Related Solutions
Critical Systems, Engineered for What’s Next
Let us evaluate your requirements and design the right scalable, secure and efficient system architecture.